Blog

How to Use an Eyewash Testing Gauge

Eyewash testing gauges are an important tool when testing eyewashes and eye/face washes for ANSI Z358.1 compliance. Make sure you are utilizing it correctly with this quick guide.

HOW TO USE AN EYEWASH GAUGE

To determine a suitable eyewash pattern, the eyewash testing gauge should be a minimum of 4 inches in length with two sets of parallel lines equidistant from the center. The interior of the lines should be 3.25 inches apart. (Section 5.1.8)

STEP 1. Activate the eye/face wash. Note: If the eye/face wash is a part of a combination unit, ensure all other outlets are activated to confirm proper flow and simultaneous use. (Section 7.1)

STEP 2. Place the testing gauge in the streams of the eyewash. (Section 5.1.8)

STEP 3. The flushing fluid should cover the areas between the interior and exterior lines of the gauge at some point less than 8 inches above the eyewash nozzle. (Section 5.1.8)

Order a Haws model 9015 eyewash gauge

Haws Crossover Tool

Your Feedback Matters!

At Haws, we’re committed to improving your experience. Please take a moment to complete our customer engagement survey for a chance to win a $250 gift card as our thank you.

Enter to Win!
Haws Co
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.