TWBS.EWE – Thermostatic Mixing Valve

Model TWBS.EWE, low-lead Emergency Valve (patent pending) thermostatically mixes hot and cold water to provide a safe fluid supply for emergency eyewash equipment. The valve contains a secondary high temperature limit valve to provide additional protection to the user in the event of main tempering valve malfunction. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

Listings: CSA certified per ASSE 1071, ANSI Z358.1, applicable sections of CSA B125.3, NSF/ANSI 372, NSF/ANSI 61-section 8, California Health and Safety Code 116875 (AB 1953).

TWBS.HF – Thermostatic Mixing Valve

Model TWBS.HF, low-lead Emergency Valve (patent pending), thermostatically mixes hot and cold water to provide a safe fluid supply for emergency shower and eyewash equipment. The valve contains a secondary high temperature limit valve to provide additional protection to the user in the event of main tempering valve malfunction. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a pressure sensing diverter valve is provided that sends a pressure signal to open the cold water by-pass valve in the event of hot water pressure loss, main valve thermostat malfunction, or clogged cold water check-stop. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

Listings: CSA certified per ASSE 1071, ANSI Z358.1, applicable sections of CSA B125.3, NSF/ANSI 372, NSF/ANSI 61-section 8, California Health and Safety Code 116875 (AB 1953).

TWBS.SHE – Thermostatic Mixing Valve

Model TWBS.SHE, low-lead Emergency Valve (patent pending), thermostatically mixes hot and cold water to provide a safe fluid supply for emergency shower and eyewash equipment. The valve contains a secondary high temperature limit valve to provide additional protection to the user in the event of main tempering valve malfunction. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

Listings: CSA certified per ASSE 1071, ANSI Z358.1, applicable sections of CSA B125.3, NSF/ANSI 372, NSF/ANSI 61-section 8, California Health and Safety Code 116875 (AB 1953).

9202E – Thermostatic Mixing Valve

Model 9202E Emergency Valve (patent pending) thermostatically mixes hot and cold water to provide a safe fluid supply for emergency showers and eyewash equipment. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate measurement.)

CSA Listings: CSA certified per ASSE 1071, ANSI Z358.1 and applicable sections of CSA B125.3.

9201E – Thermostatic Mixing Valve

Model 9201E emergency mixing valve (patent pending) thermostatically mixes hot and cold water to provide a safe fluid supply for emergency showers and eyewash equipment. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

CSA Listings: CSA certified per ASSE 1071, ANSI Z358.1, and applicable sections of CSA B125.3.

9201EFE – Thermostatic Mixing Valve

Model 9201EFE Emergency Thermostatic Mixing Valve (patent pending) thermostatically mixes hot and cold water to provide a safe fluid supply for emergency eyewash equipment. Additionally, to ensure a fail-safe water supply for emergency eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

CSA Listings: CSA certified per ASSE 1071, ANSI/ISEA Z358.1 and applicable sections of CSA B125.3.

9201EW – Thermostatic Mixing Valve

Model 9201EW Emergency Valve thermostatically mixes hot and cold water to provide a safe fluid supply for a single emergency eye/face wash. Additionally, to ensure a fail-safe water supply for emergency eyewash stations, a cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet (1.52 to 2.44 m) downstream for the most accurate temperature measurement.)

CSA Listings: CSA certified per ASSE 1071, ANSI/ISEA Z358.1, NSF/ANSI/CAN 372, and applicable sections of CSA B125.3.

9201H – Thermostatic Mixing Valve

Model 9201H, low-lead Emergency Valve (patent pending), thermostatically mixes hot and cold water to provide a safe fluid supply for emergency showers and eyewash equipment. The valve contains a secondary high temperature limit valve to provide additional protection to the user in the event of main tempering valve malfunction. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss. (No gauges supplied – ASSE 1071 standard recommends gauges be placed 5 to 8 feet downstream for the most accurate measurement.)

Listings: CSA certified per ASSE 1071, ANSI Z358.1, applicable sections of CSA B125.3, NSF/ANSI 372, NSF/ANSI 61-section 8, California Health and Safety Code 116875 (AB 1953).

Haws Crossover Tool

Your Feedback Matters!

At Haws, we’re committed to improving your experience. Please take a moment to complete our customer engagement survey for a chance to win a $250 gift card as our thank you.

Enter to Win!
Haws Co
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.